Specification

Electrical


Input Voltage / frequency (Note 2): 380…480 V (Nominal 415 V), -10%, +5%, 3-Phase, 3-Wire, 50 Hz (60 Hz optional), +/-5%

Output voltage : 600…720 Vdc (Nominal 620 Vdc) according to input voltage selection, +/-2%

Model AMT-AFC (Note 2) Input capacity (kVA) Input current (Continuous) (A) Input current (60 sec) (A) Applicable VFD Rating (kW) Weight (kg/lb) Frame
-018-4 22 30 36 18.5 50/110 A
-022-4 25 35 42 22 52/114 A
-030-4 36 50 60 30 55/121 A
-037-4 43 60 72 37 55/121 A
-045-4 50 70 84 45 60/132 A
-055-4 61 85 102 55 65/143 A
-075-4 83 115 138 75 195/430 B
-090-4 101 140 168 90 210/463 B
-110-4 122 170 204 110 225/496 B
-132-4 144 200 240 132 250/551 B
-160-4 176 245 294 160 300/661 B
-200-4 219 305 366 200 335/738 B
-250-4 273 380 456 250 360/794 B
-315-4 341 475 570 315 410/904 B
-355-4 388 540 648 355 Consult Factory
-400-4 438 610 732 400
-450-4 492 685 822 450
-500-4 546 760 912 500

Control Functions

Control mode & method Constant voltage & Hysteresis current control
Input current distortion (%THD) Less than 5% (at 100% load)
Input power factor 0.99 (at 100% load & nominal voltage), better than 0.95 (at more than 30% load)
Programmable between 0.95 leading to 0.95 lagging
Regeneration mode Yes (Automatic)
Max. switching Frequency 5 kHz
Efficiency Approx. 98%

Operation Specifications

Digital inputs 5-Programmable sequence inputs, sink/source changeable and Active Close / Active Open Selectable
Digital outputs 4-Programmable sequence outputs, open collector type
Potential free contacts 3-programmable relays 1-NO, 1-NC for 5 A @ 240Vac
Programmable between 12 different options
Programmable analog outputs 2-Programmable analog outputs AO1 & AO2: Voltage (0...10) V / Current (4...20) mA with settable Gain, Bias, Min. and Max. scaling
Soft-charge Within 5 seconds
Auto start Yes, AFC can start at power ON condition in local and serial mode.
Auto restart Adjustable up to ten times for faults like over current fault, timed over current fault, adjustable over current fault, DC bus over voltage fault, DC bus under voltage fault, earth fault, temperature fault, external fault, R-phase temperature fault, Y-phase temperature fault, B-phase temperature fault

Display Indications

Display and Keypad module Digital Operation Panel 128 x 64 Graphical LCD with white back light LED, 8-Key
keypad, 3-Status indicating LED for Run, Stop and Fault; Real Time Clock
VL-L, THDi, THDv, Line Frequency, DC bus voltage, PF, DPF, kW, kWH import, kWH export, kWH net, kVA, kVAR, Source side
current for each phase

Communication

Network connectivity RS-485 for PC interface with Modbus-RTU protocol and Wi-Fi connectivity as standard (DeviceNet, Profibus DP (Slave), CANopen, Ethernet, ControlNet are optional)

Protective Specifications

Protective function Over current DC bus over voltage External fault
Adjustable over current Over temperature Charging Fault
Timed over current Phase loss EEPROM fault
DC bus under voltage Ground fault
Fault history Last 20 faults stored in non-volatile memory with status at the time of fault
Electronic thermal overload 120% Overload for 60 Seconds

Environment

Installation Location Indoor
Type of cooling Forced Air Cooling
Ambient Temperature -15...45 °C (5...113 °F), derate the output current by 3 % /1 °C (1.8 °F) above 45 °C (113 °F), maximum up to 55 °C (131 °F) temperature
Storage Temperature -20...70 °C (-4...158 °F)
Audible Noise ≤ 72 dB @1.0m (3ft)
Altitude (above sea level) 1000 m (3300 ft) without derating, above this derate by 1% per 100 m (330 ft) above 1000 m (3300 ft)
Relative Humidity 0...95% max non condensing

Mechanical Specifications

Color RAL 7035
Protection class
A = IP 00
B = IP 31
Dimensions (W X D X H) in mm [inch] (Note 3, 4)
A = 310x360x900
[12.2x14.2x35.4]
B = 600x600x1995
[23.6x23.6x78.5]
Installation
A = Wall mounting
B = Floor mounting

Reference standard

Harmonic IEEE 519-2022, G5/4-1, GB/T 14549-93, IEC 61000-3-2, IEC 61000-3-4
Safety IEC 50178
    Note:
  1. All performance specifications are valid at nominal ratings.
  2. For higher rating model and 500...690V model requirements, contact Amtech Sales Representative.
  3. Panel fan height is included in the dimension of floor mounted unit but panel plinth height is not included in the dimension. Standard plinth height is 100 mm.
  4. All models have bottom cable entry and front access.